Shanghai Shenglin M&E Technology Co., Ltd.

Home
Products
About Us
Factory Tour
Quality Control
Contact Us
Request A Quote
Home ProductsRooftop AC unit

Commercial 50 Ton R410a Rooftop AC Unit With Fin Heat Exchanger

Certification
China Shanghai Shenglin M&E Technology Co., Ltd. certification
China Shanghai Shenglin M&E Technology Co., Ltd. certification
I'm Online Chat Now

Commercial 50 Ton R410a Rooftop AC Unit With Fin Heat Exchanger

Commercial 50 Ton R410a Rooftop AC Unit With Fin Heat Exchanger
Commercial 50 Ton R410a Rooftop AC Unit With Fin Heat Exchanger

Large Image :  Commercial 50 Ton R410a Rooftop AC Unit With Fin Heat Exchanger

Product Details:

Place of Origin: China
Brand Name: Shenglin
Certification: CE
Model Number: SRF Series

Payment & Shipping Terms:

Minimum Order Quantity: 1
Packaging Details: Stretch film+ pallet for container loading
Delivery Time: 40~45days
Payment Terms: T/T, Western Union
Supply Ability: 50~100 units/ month
Detailed Product Description
Heat Pump Type: Cooling & Heating Compressor Type: Scroll
Evaporator Type: Fin Heat Exchanger Condenser Type: Fin Heat Exchanger
Operating Voltage: 380~400V 3N 50HZ Refrigerant: R407C Or R22
Warranty: 18 Months After Leaving Factory Or 12 Months After Installation Supply Fan: Centrifugal
Mounting: Floor Standing Keyword: Rooftop Ac Units
High Light:

R410a Rooftop AC unit

,

50 Ton Rooftop AC unit

,

R410a ac unit roof stand

Custom Commercial 50 Ton R410a Rooftop Package Central Air Conditioner
 
Rooftop Ac Units​ Feature:
Capacity: 12~36kw, 3.5~10Tons.
Efficiency: 2.7~3.3 cop.
Warranty: Compressor- 3 years limited. other parts-1 year limited.
 

Structure
Panels and frameMade from galvanized steel protected with polyester powder painting to ensure total resistance to atmospheric agents.
CoilDirect expansion coils with condensate drain tray.
Hermetic compressorHigh-efficiency scroll compressor for the whole range, with built-in thermal overload cut-out and crankcase heater, mounted on rubber .
Vibration damperRipple type acoustic insulation for compressor section, and thermal insulation for coil and fan section, low noise.
Centrifugal fanForward curve centrifugal fans for air treatment section and axial fans for condensation section. Front, side, and underside air discharge of the treatment unit. High external pressure, long air supply distance.
Electric panelThe electric panel consists of breakers and contactors for compressors and fan motors, phase sequence relay, and other necessary protection devices for the main components.
Easy operation line controllerCooling/Heating/Auto. Error indication. Timing on/off.
 
 
Technical paramater:
ModelSRF12ZASRF 15ZASRF18ZASRF24ZASRF30ZASRF35ZA
SF12ZASF15ZASF18ZASF24ZASF30ZASF35ZA
Nominal cooling capacitykW1215.217.52430.335.6
Nominal heating capacitykW13.216.618.426.533.337.7
Energy regulation%0,100%0,50,100%
Power supply380V / 3Ph / 50HZA
Cooling input capacitykW4.15.35.58.811.312.3
Heating input capacitykW3.84.85.18.210.411.3
Start currentA486263637476
Cooling running currentA7.49.710.216.121.223.3
Heating running currentA6.99.29.715.120.122.2
Throttling methodThermal expansion valve
Cooling system111122
RefrigerantR410A
CompressorTypeHermetic scroll compressor
Qty111122
Condensation side 
CondenserTypeCopper tube and aluminum fin
Qty111111
Drive typeDirect drive
Motor powerkW0.250.370.370.550.750.75
Air volumem3 /h46007800780090001260012600
Evaporation side 
EvaporatorTypeCopper tube and aluminum fin
Qty111111
Motor powerkW0.320.370.451.11.52.2
Air volumem3 /h210026003400410052006300
Drive typeDirect drivePulley
Static pressure(Pa)100100100200200250
FilterAluminum filter G3
Noise dB(A)676768717272
Refrigerant filling volume(kg)3.13.14.32x3.12x3.12x4.3
Overall dimensionsLength(mm)mm141014101410197819781978
Width(mm)mm110011001100117511751175
Height(mm)mm109510951095109510951095
Weightkg240260290420480500
 
Note:
1. Nominal cooling capacity is under nominal air volume, indoor DB/WB temperature is 27℃/19℃ and outdoor DB/WB temperature is 35℃/24℃ condition;
2. Nominal heating capacity is under nominal air volume, indoor DB/WB temperature is 20℃/15℃ and outdoor DB/WB temperature is 7℃/6℃ condition;

 
Application:
Residential, office building, shopping mall...
 

Packing:
Commercial 50 Ton R410a Rooftop AC Unit With Fin Heat Exchanger 0Commercial 50 Ton R410a Rooftop AC Unit With Fin Heat Exchanger 1Commercial 50 Ton R410a Rooftop AC Unit With Fin Heat Exchanger 2Commercial 50 Ton R410a Rooftop AC Unit With Fin Heat Exchanger 3

 

After-Sales Service:
1. If the project needs our installation guidance, we can send our engineer and translator, but not free. We can also send customers installation video to teach them how to fix and operate with our product.
2. Usually, our product warranty is 18 months after leaving factory or 12 months after installation. within this months, all parts broken will be responsible for our factory.
 

Contact Details
Shanghai Shenglin M&E Technology Co., Ltd.

Contact Person: Sunny

Tel: +8613916639154

Send your inquiry directly to us (0 / 3000)