Shanghai Shenglin M&E Technology Co., Ltd.

Home
Products
About Us
Factory Tour
Quality Control
Contact Us
Request A Quote
Home ProductsRooftop Packaged Units

120kw Rooftop Packaged Units / HVAC Air Conditioner Nominal Cooling

Certification
China Shanghai Shenglin M&E Technology Co., Ltd. certification
China Shanghai Shenglin M&E Technology Co., Ltd. certification
I'm Online Chat Now

120kw Rooftop Packaged Units / HVAC Air Conditioner Nominal Cooling

large.img.alt
large.img.alt

Large Image :  120kw Rooftop Packaged Units / HVAC Air Conditioner Nominal Cooling

Product Details:

Place of Origin: China
Brand Name: Shenglin
Certification: CE
Model Number: SRF Series

Payment & Shipping Terms:

Minimum Order Quantity: 1
Price: 3200~30000USD/unit
Packaging Details: Stretch film+ pallet for container loading, plywood box for less container loading. Also can be customized.
Delivery Time: 40~45days
Payment Terms: T/T, Western Union
Supply Ability: 50~100 units/ month
Detailed Product Description
Heat Pump Type: Cooling And Heating Compressor Type: Hermetic Scroll Compressor
Evaporator Type: High Efficiency Fin Heat Exchanger Condenser Type: High Efficiency Fin Heat Exchanger
Operating Voltage: 380/400V; 3P; 50Hz/60Hz Refrigerant: Or R22
Warranty: Compressor- 3 Years Limited. Other Parts-1 Year Limited. Supply Fan: Centrifugal Or EC Fan
Keyword: Rooftop Packaged Units
High Light:

120kw Rooftop Packaged Units

,

Nominal cooling Rooftop Packaged Units

,

Hermetic scroll Heating package ac unit

R407C 120~300kw Commercial Rooftop Air Conditioner 

 

Capacity: 120~300kw, 35~86Tons.
Efficiency: 2.7~3.3 cop.
Warranty: Compressor- 3 years limited. other parts-1 year limited.
Air flow: 63000~162000m3/h


Main Features Of Rooftop Packaged Units

Renewable Energy

High efficiency and energy saving

Advanced technology and convenient operation

Wide application range

 
Technical paramater:
 
Model SRF120ZA SRF140ZA SRF150ZA SRF180ZA SRF210ZA SRF300ZA
SF120ZA SF140ZA SF150ZA SF180ZA SF210ZA SF300ZA
Nominal cooling capacity kW 120 140 149 180 210 298
Nominal heating capacity kW 128.3 150 159.2 192.5 226 318

Energy regulation

 

% 0,25,50,75,100 0,50,100 0,16.6,33.3,50,66.4,83,100 0,25,50,75,100
Power supply 380V / 3Ph / 50HZA
Cooling input capacity kW 45.1 55.7 55.1 69.9 83 106.7
Heating input capacity kW 41.7 51.8 51.5 64.8 77 100
Start current A 218 252 323 232 301 415
Cooling running current A 82.4 101.4 100.2 130.9 151 192.3
Heating running current A 77.4 95.7 95.1 123.5 142.3 184.3
Throttling method Thermal expansion valve
Cooling system 4 4 2 6 6 4
Refrigerant R410A
Compressor Type Hermetic scroll compressor 380V / 3Ph / 50HZA
Qty 4 4 2 6 6 4
Condensation side
Condenser Type Copper pipe copper fin
Fan Qty 2 2 2 4 4 4
Drive type Direct drive
Motor power kW 2X1.5 2x2.2 2x2.2 4X1.1 4X1.5 4x2.2
Air volume m3 /h 42000 54000 54000 66000 84000 108000
Evaporation side  
Evaporator Type Copper pipe copper fin
  Qty 1 1 1 1 1 1
Motor power kW 7.5 11 11 15 15 18.5
Air volume m3 /h 21000 25000 26000 32000 38000 54000
Drive type Pulley
Static pressure(Pa) 400 400   500 500 500
Filter Aluminum filter G3
Noise dB(A) 75 79 79 80 80 82
Refrigerant filling volume(kg) 4x7.5 4x8.5 2x17 6x7.5 6x8.5 4x14
Overall dimensions Length(mm) mm 3626 3626 3626 4690 4690 5660
Width(mm) mm 2200 2200 2200 2330 2330 2330
Height(mm) mm 2047 2047 2047 2055 2427 2055
Weight kg 1710 1820 1850 2180 2430 2860
Note: 1. Nominal cooling capacity is under nominal air volume, indoor DB/WB temperature is 27℃/19℃ and outdoor DB/WB temperature is 35℃/24℃ condition;
2. Nominal heating capacity is under nominal air volume, indoor DB/WB temperature is 20℃/15℃ and outdoor DB/WB temperature is 7℃/6℃ condition;

 

Application:

Used in a large number of fresh air and exhaust air conditioning system.
Such as laboratory, for security needs, must be a lot of wind, which also need to add fresh air, if you can recover the energy of exhaust, to preheat or pre cooling fresh air can be a lot of energy.
Full heat recovery can recover latent heat, and partial heat recovery can not be.
Where it can achieve the recovery of phase change heat of the occasion, can use the full heat recovery technology.

Contact Details